RSD Model Selection
| Enter your specific system conditions and select the right tower, print custom submittals, and more. |
- Waterflow (Gallons per Minute)
- Load (BTUs per Hour)
Applications for RSD Models
| Application information for RSD Tower models. |
| TYPE OF EQUIPMENT |
BTU |
GPM |
COOLING RANGE (F) |
| Air Conditioning or Refrigeration |
Per Ton |
Per Ton |
|
Hermetic/Semi-hermetic compressor
Open drive compressor (external motor)
Steam turbine driven compressor
Absorption chillier |
15,000/hr
12,000/hr
30,000/hr
30,000/hr |
1.5-3
3-3.6
2-3
3-4 |
10-20
10-12
20-30
15-20 |
| Diesel Engine Jacket Water & Lube Oil |
Four-cycle supercharged
Four-cycle non supercharged |
2,600/hr
3,000/hr |
0.26
0.30 |
20
20 |
| Natural Gas Engine Jacket Water & Lube Oil |
Per/BHP |
Per/BHP |
|
Four-cycle engine
Two-cycle engine |
4,500/hr
4,500/hr |
0.45
0.45 |
20
20 |
| Electric Motor Driven Air Compressors |
Per/BHP |
Per/BHP |
|
Single stage
Single stage, with aftercooler
Two stage, with intercooler |
380/hr
2,545/hr
1,530/hr |
0.076
0.51
0.31 |
10
10
10 |
| Plastic Injection Machines |
Refer to the Hydraulic load demand |
| Hydraulic Oil Coolers |
2,545/hr/bhp |
.51/bhp |
10 |
| Welding Tip Coolers |
84/min(avg.) |
1 |
10 |
| Dry Cleaning Machines |
5,000 btu/lb cap. |
3 gpm/ton |
10.00 |
Whenever possible calculate actual values as follows:
Load in btu/hr = (range x gpm) x 500
Cooling Range = (btu load/gpm)/500
GPM = (btu load/range)/500
Cooling Range = (inlet to tower - desired outlet)
|
bhp = Brakehorse power
gpm = Gallons per minute
500 = 8.33lb/gal x 60 minutes
1 ton = 15,000 btu/hr
|
For more information on tower selection refer to your RSD Fiberglass Cooling Tower Catalog.
|