Log in | Register | Saturday, May 19th 2012
RSD Model Selection
Enter your specific system conditions and select the right tower, print custom submittals, and more.


  • Waterflow (Gallons per Minute)
  • Load (BTUs per Hour)






Applications for RSD Models
Application information for RSD Tower models.
TYPE OF EQUIPMENT BTU GPM COOLING RANGE (F)
Air Conditioning or Refrigeration Per Ton Per Ton  
Hermetic/Semi-hermetic compressor
Open drive compressor (external motor)
Steam turbine driven compressor
Absorption chillier
15,000/hr
12,000/hr
30,000/hr
30,000/hr
1.5-3
3-3.6
2-3
3-4
10-20
10-12
20-30
15-20
Diesel Engine Jacket Water & Lube Oil
Four-cycle supercharged
Four-cycle non supercharged
2,600/hr
3,000/hr
0.26
0.30
20
20
Natural Gas Engine Jacket Water & Lube Oil Per/BHP Per/BHP  
Four-cycle engine
Two-cycle engine
4,500/hr
4,500/hr
0.45
0.45
20
20
Electric Motor Driven Air Compressors Per/BHP Per/BHP  
Single stage
Single stage, with aftercooler
Two stage, with intercooler
380/hr
2,545/hr
1,530/hr
0.076
0.51
0.31
10
10
10
Plastic Injection Machines Refer to the Hydraulic load demand
Hydraulic Oil Coolers 2,545/hr/bhp .51/bhp 10
Welding Tip Coolers 84/min(avg.) 1 10
Dry Cleaning Machines 5,000 btu/lb cap. 3 gpm/ton 10.00

Whenever possible calculate actual values as follows:

Load in btu/hr = (range x gpm) x 500
Cooling Range = (btu load/gpm)/500
GPM = (btu load/range)/500
Cooling Range = (inlet to tower - desired outlet)
bhp = Brakehorse power
gpm = Gallons per minute
500 = 8.33lb/gal x 60 minutes
1 ton = 15,000 btu/hr